Information about Electricity Distribution
Electricity distribution is the penultimate stage in the delivery (before retail) of electricity to end users. It is generally considered to include medium-voltage (less than 50 kV) power lines, electrical substations and pole-mounted transformers, low-voltage (less than 1000 V) distribution wiring and sometimes electricity meters.
History
In the early days of electricity distribution, direct current DC generators were connected to loads at the same voltage. The generation, transmission and loads had to be of the same voltage because there was no way of changing DC voltage levels, other than inefficient motor-generator sets. Low DC voltages were used (on the order of 100 volts) since that was a practical voltage for incandescent lamps, which were then the primary electrical load. The low voltage also required less insulation to be safely distributed within buildings.The losses in a cable are proportional to the square of the current, the length of the cable, and the resistivity of the material, and are inversely proportional to cross-sectional area. Early transmission networks were already using copper, which is one of the best economically feasible conductors for this application. To reduce the current and copper required for a given quantity of power transmitted would require a higher transmission voltage, but no convenient efficient method existed to change the voltage level of DC power circuits. To keep losses to an economically practical level the Edison DC system needed thick cables and local generators. Early DC generating plants needed to be within about 1.5 miles of the farthest customer to avoid the need for excessively large and expensive conductors.
Introduction of alternating current
The adoption of alternating current (AC) for electricity generation following the War of Currents dramatically changed the situation. Power transformers, installed at power stations, could be used to raise the voltage from the generators and transformers at local substations reduced it to supply loads. Increasing the voltage reduced the current in the transmission and distribution lines and hence the size of conductors required and distribution losses incurred. This made it more economical to distribute power over long distances. Generators (such as hydroelectric sites) could be located far from the loads.In North America, early distribution systems used a voltage of 2200 volts corner-grounded delta. Over time, this was gradually increased to 2400 volts. As cities grew, most 2400 volt systems were upgraded to 4160/2400 volt, three-phase systems. Some city and suburban distribution systems continue to use this range of voltages, but most have been converted to 7200/12470Y, 7620/13200Y, 14400/24940Y, and 19920/34500Y.
European systems used 3300 volts to ground, in support of the 220/380Y volt power systems used in those countries. In the UK, urban systems progressed to 6.6 kV and then 11 kV (phase to phase), the most common distribution voltage.
North American and European power distribution systems also differ in that North American systems tend to have a greater number of low-voltage, step-down transformers located close to customers' premises. For example, in the US a pole-mounted transformer in a suburban setting may supply 1-3 houses, whereas in the UK a typical urban or suburban low-voltage substation would normally be rated between 315kVA and 1000kVA (1MVA) and supply a whole neighbourhood. This is because the higher voltage used in Europe (415V vs 230V) may be carried over a greater distance with acceptable power loss. An advantage of the North American setup is that failure or maintenance on a single transformer will only affect a few customers. Advantages of the UK setup are that the transformers may be fewer, larger and more efficient, and due to diversity there need be less spare capacity in the transformers, reducing power wastage. In North American city areas with many customers per unit area, network distribution will be used, with multiple transformers and low-voltage busses interconnected over several city blocks.
Rural Electrification systems, in contrast to urban systems, tend to use higher voltages because of the longer distances covered by those distribution lines (see Rural Electrification Administration). 7200, 12470, 25000, and 34500 volt distribution is common in the United States; 11 kV and 33 kV are common in the UK, New Zealand and Australia; 11 kV and 22 kV are common in South Africa. Other voltages are occasionally used.
In New Zealand, Australia, Saskatchewan, Canada, and South Africa, single wire earth return systems (SWER) are used to electrify remote rural areas.
While power electronics now allow for conversion between DC voltage levels, AC is still used in distribution due to the economy, efficiency and reliability of transformers. High-voltage DC is used for transmission of large blocks of power over long distances, or for interconnecting adjacent AC networks, but not for distribution to customers.
Distribution network configurations
Distribution networks are typically of two types, radial or interconnected (see Spot Network Substations). A radial network leaves the station and passes through the network area with no normal connection to any other supply. This is typical of long rural lines with isolated load areas. An interconnected network is generally found in more urban areas and will have multiple connections to other points of supply.These points of connection are normally open but allow various configurations by the operating utility by closing and opening switches. Operation of these switches may be by remote control from a control centre or by a lineman. The benefit of the interconnected model is that in the event of a fault or required maintenance a small area of network can be isolated and the remainder kept on supply.
Within these networks there may be a mix of overhead line construction utilizing traditional utility poles and wires and, increasingly, underground construction with cables and indoor or cabinet substations. However, underground distribution is significantly more expensive than overhead construction. In part to reduce this cost, underground power lines are sometimes co-located with other utility lines in what are called Common utility ducts. Distribution feeders emanating from a substation are generally controlled by a circuit breaker which will open when a fault is detected. Automatic Circuit Reclosers may be installed to further segregate the feeder thus minimising the impact of faults.
Long feeders experience voltage drop requiring capacitors or voltage regulators to be installed.
Characteristics of the supply given to customers are generally mandated by contract between the supplier and customer. Deviations from the normal usage pattern usually invoke monthly surcharges. Variables include:
- AC or DC - Virtually all public electricity supplies are AC today. Users of large amounts of DC power such as some electric railways, telephone exchanges and industrial processes such as aluminium smelting either operate their own or have adjacent dedicated generating equipment, or use rectifiers to derive DC from the public AC supply
- Voltage, including tolerance (usually +10 or -15 percentage)
- Frequency, commonly 50 & 60 Hz, 16-2/3 Hz for some railways and, in a few older industrial and mining locations, 25 Hz
- Phase configuration (single phase, polyphase including two phase and three phase)
- Maximum demand (usually measured as the largest amount of power delivered within a 15 or 30 minute period during a billing period)
- Load Factor, expressed as a ratio of average load to peak load over a period of time. Load factor indicates the degree of effective utilization of equipment (and capital investment) of distribution line or system.
- Power factor of connected load
- Earthing arrangements - TT, TN-S, TN-C-S or TN-C
- Maximum prospective short circuit current
- Maximum level and frequency of occurrence of transients
Modern Distribution Systems
The modern distribution system begins as the primary circuit leaves the sub-station and ends as the secondary service enters the customer's meter socket. A variety of methods, materials, and equipment are used among the various utility companies across the U.S., but the end result is similar. First, the energy leaves the sub-station in a primary circuit, usually with all three phases.The most common type of primary is known as a wye configuration (so named because of the shape of a "Y".) The wye configuration includes 3 phases (represented by the three outer parts of the "Y") and a neutral (represented by the center of the "Y".) The neutral is grounded both at the substation and at every power pole. In a typical 12470Y/7200 volt system, the pole mount transformer's primary winding is rated for 7200 volts and is connected across one phase of power and the neutral. The primary and secondary (low voltage) neutrals are bonded (connected) together to provide a path to blow the primary fuse if any fault occurs that allows primary voltage to enter the secondary lines. An example of this type of fault would be a primary phase falling across the secondary lines. Another example would be some type of fault in the transformer itself.
The other type of primary configuration is known as delta, this method is older and less common. Delta is so named because of the shape of the Greek letter delta, a triangle. Delta has only 3 phases and no neutral. In delta there is only a single voltage, between two phases (phase to phase), while in wye there are two voltages, between two phases and between a phase and neutral (phase to neutral). Wye primary is safer because if one phase becomes grounded, that is makes connection to the ground through a person, tree, or other object, it should trip out the fused cutout similar to a household circuit breaker tripping. In delta, if a phase makes connection to ground it will continue to function normally. It takes two or three phases to make connection to ground before the fused cutouts will open the circuit. The voltage for this configuration is usually 4800 volts. Transformers are sometimes used to step down from 7200 or 7600 volts to 4800 volts or to step up from 4800 volts to 7200 or 7600 volts. When the voltage is stepped up, a neutral is created by bonding one leg of the 7200/7600 side to ground. This is commonly used to power single phase underground services or whole housing developments that are built in 4800 volt delta distribution areas. Step downs are used in areas that have been upgraded to a 7200/12500Y or 7600/13200Y and the power company chooses to leave a section as a 4800 volt setup. Sometimes power companies choose to leave sections of a distribution grid as 4800 volts because this setup is less likely to trip fuses or reclosers in heavily wooded areas where trees come into contact with lines.
Economic and Political
In the United States, Electric industry "deregulation" reform, started in the mid-1990s, has led to the creation of electricity markets through the elimination of the former so called natural monopoly of generation, transmission, and distribution. As a consequence, electricity has become more of a commodity. The separation has also led to the development of new terminology to describe the business units, e.g. line company, wires business and network company.- ;;
See also
- Blackout
- Busbar
- Common utility duct
- Cutout
- Electrical utility
- Distributed generation
- Electrical wiring
- Electricity generation
- Electricity transmission
- Electricity retailing
- Future energy development
- Lineman
- Load Profile
- Net metering
- Power cable
- Power quality
- V2G
- Virtual power plant
- Voltage drop
References
External links
- IEEE Power Engineering Society
- IEEE Power Engineering Society Distribution Subcommittee
- U.S. Department of Energy Electric Distribution website
- Inter-Utility Overhead Training Association
- Inter-Utility Substation Training Association
- Electrical Basics Courses
Further reading
- Brown, R. E., Electric Power Distribution Reliability, Marcel Dekker, Inc., 2002.
- Burke, J., Power Distribution Engineering, Marcel Dekker, Inc., 1994.
- Hoffman, P., Scheer, R., Marchionini, B., Distributed Energy Resources: A Key Element of Grid Modernization DE - March/April 2004 http://www.forester.net/de_0403_distributed.html
- Short, T. A. Electric Power Distribution Handbook, CRC Press, 2004.
- Westinghouse Electric Corporation, Distribution Systems, vol. 3, 1965.
- Westinghouse Electric Corporation, Electric power transmission patents; Tesla polyphase system. (Transmission of power; polyphase system; Tesla patents)
- Willis, H. L., Power Distribution Planning Reference Book, Marcel Dekker, Inc., 2nd ed., 2004.
Electricity delivery is the process that goes from generation of electricity in the power station to the use by the consumer.
The main processes in power delivery are, by order:
..... Click the link for more information.
The main processes in power delivery are, by order:
- Central generation
- Transmission
- Distribution
- And retailing
..... Click the link for more information.
Electricity retailing is the final process in the delivery of electricity from generation to the consumer. The other main processes are transmission and distribution.
..... Click the link for more information.
Beginnings
..... Click the link for more information.
Electricity (from New Latin ēlectricus, "amberlike") is a general term for a variety of phenomena resulting from the presence and flow of electric charge. This includes many well-known physical phenomena such as lightning, electromagnetic fields and electric currents,
..... Click the link for more information.
..... Click the link for more information.
electrical substation is a subsidiary station of an electricity generation, transmission and distribution system where voltage is transformed from high to low or the reverse using transformers.
..... Click the link for more information.
..... Click the link for more information.
transformer is a device that transfers electrical energy from one circuit to another through inductively coupled wires. A changing current in the first circuit (the primary
..... Click the link for more information.
..... Click the link for more information.
An electric meter or energy meter is a device that measures the amount of electrical energy supplied to a residence or business. These are customers of an electric company.
The most common type is more properly known as a (kilo)watt-hour meter or a joule meter.
..... Click the link for more information.
The most common type is more properly known as a (kilo)watt-hour meter or a joule meter.
..... Click the link for more information.
alternating current (AC) is an electrical current whose magnitude and direction vary cyclically, as opposed to direct current, whose direction remains constant. The usual waveform of an AC power circuit is a sine wave, as this results in the most efficient transmission of
..... Click the link for more information.
..... Click the link for more information.
Electricity generation is the first process in the delivery of electricity to consumers. The other processes are electric power transmission and electricity distribution which are normally carried out by the electrical power industry.
..... Click the link for more information.
..... Click the link for more information.
In the "War of Currents" era (sometimes, "War of the Currents" or "Battle of Currents") in the late 1880s, George Westinghouse and Thomas Edison became adversaries due to Edison's promotion of direct current (DC) for electric power distribution over the
..... Click the link for more information.
..... Click the link for more information.
transformer is a device that transfers electrical energy from one circuit to another through inductively coupled wires. A changing current in the first circuit (the primary
..... Click the link for more information.
..... Click the link for more information.
A power station (also referred to as generating station or power plant) is an industrial facility for the generation of electric power.[1][2][3]
Power plant
..... Click the link for more information.
Power plant
..... Click the link for more information.
electrical substation is a subsidiary station of an electricity generation, transmission and distribution system where voltage is transformed from high to low or the reverse using transformers.
..... Click the link for more information.
..... Click the link for more information.
Hydroelectricity is electricity produced by hydropower. Hydroelectricity now supplies about 715,000 MWe or 19% of world electricity (16% in 2003), accounting for over 63% of the total electricity from renewables in 2005.
..... Click the link for more information.
..... Click the link for more information.
Rural electrification is the process of bringing electrical power to rural and remote areas. Electricity is used not only for lighting and household purposes, but it also allows for mechanization of many farming operations, such as threshing, milking, and hoisting grain for
..... Click the link for more information.
..... Click the link for more information.
The Rural Electrification Administration (REA) was an agency of the United States federal government created on 11 May 1935 through efforts of the administration of President Franklin D. Roosevelt.
..... Click the link for more information.
..... Click the link for more information.
Anthem
"God Defend New Zealand"
"God Save the Queen" 1
Capital Wellington
Largest city Auckland
..... Click the link for more information.
"God Defend New Zealand"
"God Save the Queen" 1
Capital Wellington
Largest city Auckland
..... Click the link for more information.
Anthem
Advance Australia Fair [1]
Capital Canberra
Largest city Sydney
..... Click the link for more information.
Advance Australia Fair [1]
Capital Canberra
Largest city Sydney
..... Click the link for more information.
Saskatchewan
Flag Coat of arms
Motto: Multis E Gentibus Vires (Latin: "The Strength of Many Peoples")
Capital Regina
Largest city Saskatoon
Official languages English
Government
..... Click the link for more information.
Flag Coat of arms
Motto: Multis E Gentibus Vires (Latin: "The Strength of Many Peoples")
Capital Regina
Largest city Saskatoon
Official languages English
Government
..... Click the link for more information.
..... Click the link for more information.
Single wire earth return (SWER) or single wire ground return is a single-wire transmission line for supplying single-phase electrical power to remote areas at low cost.
..... Click the link for more information.
..... Click the link for more information.
HVDC or high-voltage, direct current electric power transmission systems contrast with the more common alternating current systems as a means for the bulk transmission of electrical power.
..... Click the link for more information.
..... Click the link for more information.
In electricity distribution networks, spot network substations are used in interconnected distribution networks. They have the secondary network (also called a grid network) with all supply transformers bussed together on the secondary side at one location.
..... Click the link for more information.
..... Click the link for more information.
Fault may refer to:
..... Click the link for more information.
- Fault (geology), planar rock fractures which show evidence of relative movement
- Fault (technology), an abnormal condition or defect at the component, equipment, or sub-system level which may lead to a failure
..... Click the link for more information.
utility pole, telegraph pole, telephone pole, power pole, or telegraph post is a post or pole upon which telecommunication network equipment is situated.
..... Click the link for more information.
..... Click the link for more information.
A common utility duct, sometimes called a common utility conduit, is any structure - above, on, or below ground - that carries more than two types of public utility lines. However, the phrase often refers specifically to underground tunnels.
..... Click the link for more information.
..... Click the link for more information.
A circuit breaker is an automatically-operated electrical switch designed to protect an electrical circuit from damage caused by overload or short circuit. Unlike a fuse, which operates once and then has to be replaced, a circuit breaker can be reset (either manually or
..... Click the link for more information.
..... Click the link for more information.
Voltage drop is the reduction in voltage in an electrical circuit between the source and load. In electrical wiring national and local electrical codes may set guidelines for maximum voltage drop allowed in a circuit, to ensure reasonable efficiency of distribution and proper
..... Click the link for more information.
..... Click the link for more information.
Contract Law
Part of the common law series
Contract
Contract formation
Offer and acceptance · Mailbox rule
Mirror image rule · Invitation to treat
Firm offer · Consideration
Defenses against formation
..... Click the link for more information.
Part of the common law series
Contract
Contract formation
Offer and acceptance · Mailbox rule
Mirror image rule · Invitation to treat
Firm offer · Consideration
Defenses against formation
..... Click the link for more information.
alternating current (AC) is an electrical current whose magnitude and direction vary cyclically, as opposed to direct current, whose direction remains constant. The usual waveform of an AC power circuit is a sine wave, as this results in the most efficient transmission of
..... Click the link for more information.
..... Click the link for more information.
Direct current (DC or "continuous current") is the constant flow of electric charge. This is typically in a conductor such as a wire, but can also be through semiconductors, insulators, or even through a vacuum as in electron or ion beams.
..... Click the link for more information.
..... Click the link for more information.
This article is copied from an article on Wikipedia.org - the free encyclopedia created and edited by online user community. The text was not checked or edited by anyone on our staff. Although the vast majority of the wikipedia encyclopedia articles provide accurate and timely information please do not assume the accuracy of any particular article. This article is distributed under the terms of GNU Free Documentation License.
Herod_Archelaus